TS-UPS35-12

Alimentation 12VDC 35 Watt avec batterie de secours

 

Catégorie : Étiquette :

Product Description

Model

SC-35-12

SC-35-24

OUTPUT

DC voltage

CH1:13.8V

CH1:13.4V

CH1:27.6V

CH2:26.5V

Voltage tolerance

±2%

 

±1%

 

Rated current

2.0A

0.5A

1.0A

0.3A

Current range

0~2.0A

 

0~1.0A

 

Rated power

34.3W

35.6W

Ripple&noise

120mvp-p

 

120mvp-p

 

DCvoltage ADJ.range

CH1:11.3~14.9V

CH1:21.3~29.8V

Setup,rise,hold time

800ms,50ms,80ms/230VAC, 1600ms,50ms,16ms/115VAC

INPUT

Voltage range

90~264VAC,127~370VDC

frequency

47~63HZ

AC current

0.9A/115VAC,0.45A/230VAC

efficiency

81%

83%

Inrush current

Cold start current 25A/115VAC,45A/230VAC

Leakage current

< 1mA/240VAC

PROTECTION

Over load

Rated output power110%~150% start over load protection

Protection type : Constant current limiting, recovers automatically after fault

condition is removed

Battery protection

9.5~11V

20~22V

At low voltage

protection mode:cutoff output

FUNCTION

UPS introduction

long-term online floating charge to battery,high charging efficiency,battery can saturate to more than 90% ,cauto-stop charging when it's full,prevent over charging. Effectively extend battery life,AC/battery auto switch ,no switch time,no need human guard,

cold-start ,when there is no AC input ,can use battery start UPS,Meet the user's emergency needs

ENVIRONMENT

Working temp,humidity

-10°C~+60°C,20%~90%RH

Storagetemp,humidity

-20°C~+85°C,10%~95%RH non-condensing

Withstand vibration

10~500HZ,2G 10min/1cycle,period for 60 minutes,each axes

SAFETY

Withstand voltage

I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC

Isolated resistance

I/P-O/P,I/P-FG,O/P-FG:100Mohms/500VDC

OTHERS

Dimension

111*78*36mm (L*W*H)

Weight

0.28kg

NOTE

1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and25°Cof

ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated

with a 0.1uf & 47uf parallel capacitor.

3. Tolerance : includes set up tolerance, line regulation and load regulation.