Alimentations Industrielle 48VDC, montage sur rail DIN puissance de 60watt, 75Watt, 120W, 240Watt
•Universal AC input / Full range
•Protections:Short circuit / Overload / Over voltage / Over temperature
•Cooling by free air convection
•Can be installed on DIN rail TS-35/7.5 or 15
•LED indicator for power on
•100% full load burn-in test
•Fix switching frequency at 50KHz
MODEL
DR-75-12
DR-75-24
OUTPUT
DC VOLTAGE
12V
24V
RATED CURRENT
6.3A
3.2A
CURRENT RANGE
0 ~ 6.3A
0 ~ 3.2A
RATED POWER
76W
76.8W
RIPPLE & NOISE (max.) Note.2
100mVp-p
150mVp-p
VOLTAGE ADJ. RANGE
12 ~ 14V
24 ~ 28V
VOLTAGE TOLERANCE Note.3
±2.0%
±1.0%
LINE REGULATION
±0.5%
LOAD REGULATION
SETUP, RISE TIME
1000ms, 60ms/230VAC 1800ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.)
60ms/230VAC 12ms/115VAC at full load
INPUT
VOLTAGE RANGE
85 ~ 264VAC 120 ~ 370VDC
FREQUENCY RANGE
47 ~63Hz
EFFICIENCY (Typ.)
76%
80%
AC CURRENT (Typ.)
1.6A/115V 0.96A/230V
INRUSH CURRENT (Typ.)
COLD START 20A/115VAC 40A/230VAC
LEAKAGE CURRENT
<1mA/ 240VAC
PROTECTION
OVERLOAD
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE
15 ~ 16.5V
29 ~ 34V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE
85°C+5°C (TSW1) detect on heat sink of power transistor
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
ENVIRONMENT
WORKING TEMP.
-10 ~ +60°C (Refer to “Derating Curve")
WORKING HUMIDITY
20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY
-20 ~ +85”C, 10 ~ 95% RH
TEMP. COEFFICIENT
±0.03%/°C (0 ~ 50°C)
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY &
EMC
(Note 4)
SAFETY STANDARDS
UL508, TUV EN60950-1 approved
WITHSTAND VOLTAGE
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25°C/ 70% RH
EMC EMISSION
Compliance to EN55011,EN55022 (CISPR22) Class B, EN61000-3-2,-3
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
OTHERS
MTBF
123.1K hrs min. MIL-HDBK-217F (25°C)
DIMENSION
55.5*125.2*100mm (W*H*D)
PACKING
0.6Kg; 20pcs/13Kg/1.29CUFT
NOTE
•Universal AC input/Full range
•Protections: Short circuit / Overload / Over voltage
•DC OK relay contact
•No load power consumptions.<0.75W
MDR-60-5
MDR-60-12
MDR-60-24
MDR-60-48
5V
48V
10A
5A
2.5A
1.25A
0 ~ 10A
0 ~5A
0 -2.5A
0-1.25A
50W
60W
RIPPLE & NOISE (max.) Nota.2
80mVp-p
120mVp-p
200mVp-p
5 -6V
12-15V
24 – 30V
48 ~ 56V
±1.5%
SETUP, RISE TIME Note.5
500ms, 30ms/230VAC 500ms, 30ms/115VAC at full load
50ms/230VAC 20ms/115VAC at full load
85 – 264VAC 120-370VDC
47 ~ 63Hz
78%
86%
88%
87%
1.8A/115VAC 1A/230VAC
COLD START 30A/115VAC,60A/230VAC
<1mA/240VAC
105 – 150% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
OVERVOLTAGE
6.25-7.25V
15.6 – 18V
31.2-36V
57.6 – 64.8V
Protection type: Shut down o/p voltage, re-power on to recover
FUNCTION
DC OK SIGNAL
Relay contact rating (max.): 30V/1A resistive
-20 – +70°C (Refer to “Derating Curve")
-40 ~ +85°C, 10 ~ 95% RH
±0.03%/°C (0 – 50°C)
Component: 10 – 500Hz, 2G 10min./1 cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, UL60950-1, TUV EN60950-1 approved
l/P-0/P:3KVAC l/P-FG:2KVAC 0/P-FG:0.5KVAC
l/P-O/P, l/P-FG, 0/P-FG:>100M Ohms/500VDC/25°C/70% RH
Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
Compliance to EN6100(M-2,3,4,5,6,8,11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
299.2K hrs min. MIL-HDBK-217F (25°C)
40*90*100mm (W*H*D)
0.33Kg; 42pcs/14.8Kg/0.82CUFT
TS-DR: Single Output DIN rail Power supply
Features :
SPECIFICATION :
Model
TS-DR-75-48
TS-DR-120-48
TS-DR-240-48
DC output voltage
Rated output current
1.6A
Wave and noise
240mVp-p
Inlet wire stability
Load stability
Efficiency
81%
85%
Adjustable range for DC voltage
±10%
Input voltage range
85~264VAC 47~63Hz;120~370VDC
Impact current
Cold-start current 20A/115V 40A/230V
Cold-start current 27A/115V 45A/230V
Overload protection
105%~150% Type: cut off the output, automatic recovery
Over-voltage protection
120%~140% shutdown O/P voltage, re-power on to recover
55~60V
Setup, rise , hold up time
1000ms, 60ms, 60ms/230VAC at full load
500ms, 70ms, 30ms/230VAC at full load
800ms, 40ms, 20ms/230VAC at full load
Withstand voltage
I/P-O/P: 1.5kV I/P-FG: 1.5kV O/P-FG: 0.5kV 1 minute
Isolation resistance
I/P-O/P I/P-FG O/P-FG: 500VDC/100MΩ
Working temperature
-10°c~+50°c
Dimension
55.5×125.2×100mm
65.5 x 125.2 x 100mm
125.5 x 125.5 x 100mm
Weight
0.55kg
0.8kg
1.2kg
Packing
42 x 25 x 24CM/24PCS/13.5kg
45.5 x 35 x 26CM/24PCS/19.2kg
41.5 x 27.5 x 25CM/12PCS/14.5kg
Marque: Telesystem